Position: Home >Product > Low frequency online UPS > 3 phase online UPS>3 phase online UPS

EST Series 200KVA online 3 phase UPS

EST Series 200KVA online 3 phase UPS
  • Model NoTT200K
  • Size1250*750*1650 & 800*750*1650(W*H*D mm)
  • Operating temperature-20~40℃

Detailed

EST series 200KVA online three phase in three phase out UPS is an on-line double-conversion UPS with output isolation transformer built-in, offering high levels of reliability and performanance for all kinds of load, not only IT systems, banking and communications, but also medical service and industrial applications, its perfect reliablity and performance make it most popular in some countries with harsh and unstable grid.

 

● Online double conversion with full DSP control; IGBT rectifier 
● pure sine wave output, zero transfer time 
● Suitable for all kinds of loads (resistive, inductive and non-linear loads ect.)
● High overload capability (up to 150%)
● Support battery cold start and auto-restart when mains power is restored
● High charging capability
● Standard configuration with output isolation transformer
● Superior protection (surgers, short-circuit, overvoltages, undervoltages, overcharge, overload, over tempretuer, reverse connection protection etc.)
● Advanced communications RS232(standard) 
● Optional configuration: USB ports,  SNMP, dry contacts and RS485
● Other options(parallel kits, input isolation transformer, bypass isolation transformer and harrmonic suppressor)
● Standard automatic and manual maintanance by pass
● LCD touch screen, friendly human & machine interface
● Front access makes maintenance and replacement easy 
● large capability of history records storage
● Optional input filter to improve input power factor                                    

● High efficiency 95%

● Low input distortion: THD < 5%
● Generator compatible
● High immunity to external disturbances 
● Optional N+X redundancy parallel up to 8 units
● 100% unbalance load capability

 

 

 

model TT200K
Norminal capacity(KW) 200/160
battery voltage 384VDC/396VDC
Charge current 20A~60A(adjustable)
Input voltage 380V±25%
Input Frequency 50/60Hz±10%
Output voltage 380V±1%
frequency Synchronized with utility in mains mode,50/60Hz±1% in battery mode
Waveform Pure Sine Wave
Total harmonic distortion Linear load<3%;non-linear load<5%
Crest factor 3:1
Protection Short-circuit,overload,overvoltage,undervoltage,low battery,overtemperature,fan fault
Inverter overload capability 125%,10min;150%,1min
Transfer time 0ms
Operating temperature -20~40
Relative humidity 0~90%
Running high(maximum) <1000(each additional 100 meters power fell 1% to a maximum 4,000 meters)
Cooling Forced ventilation
Noise ≤65DB(Distance 1m)
Size 1250*750*1650 & 800*750*1650(W*H*D mm)

 

Hits:  UpdateTime:2020-09-29 09:08:21  【Printing】  【Close